27 items
-
$0.00 /
- Approx LBS/MFT: 46
- AWG Size: 20
- Cond. Material: Bare Copper
-
$0.00 /
- Approx LBS/MFT: 148
- AWG Size: 20
- Cond. Material: Bare Copper
-
$0.00 /
- Approx LBS/MFT: 223
- AWG Size: 20
- Cond. Material: Bare Copper
-
$0.00 /
- Approx LBS/MFT: 339
- AWG Size: 20
- Cond. Material: Bare Copper
-
$0.00 /
- Approx LBS/MFT: 397
- AWG Size: 20
- Cond. Material: Bare Copper
-
$0.00 /
- Approx LBS/MFT: 786
- AWG Size: 20
- Cond. Material: Bare Copper
-
PLTC-20-16PR-SPOS$0.00 / 1000 FT
- Approx LBS/MFT: 280
- AWG Size: 20
- Cond. Material: Bare Copper
PVC/PVC Instrumentation Cable with Individual and Overall Shielded Pairs Specifications
PVC/PVC Instrumentation Cable Construction:
- Conductor: 20 AWG through 16 AWG bare, annealed copper per ASTM B3 Class B; stranding per ASTM B8
- Insulation: Polyvinylchloride (PVC)
- Color-coded per ICEA Method 1; Pairs: Black and White
- Shield: Individual and overall shielded pairs
- Individual pairs are 100% shielded with aluminum/polyester in contact with stranded tinned copper drain wire
- Overall Shield: aluminum/polyester in contact with stranded tinned copper drain wire
- Jacket: Sunlight-resistant Polyvinylchloride (PVC)
- Options:
- Tinned copper conductor, Class C Stranding
- Other constructions available upon request
PVC/PVC Instrumentation Cable Ratings and Approvals:
- Voltage Rating: 300V
- UL 13 Type PLTC/ITC
- IEEE 383 (70,000 BTU/hr)
- UL Subject 13 (70,000 BTU/hr) for PLTC
- UL Subject 2250 (70,000 BTU/hr) for ITC
- Meets EPA 40 CFR, Part 261 for leachable lead content per TCLP method
- OSHA acceptable
PVC/PVC Instrumentation Cable Applications:
- Acceptable for use in free air or raceways in accordance with NEC
- Typical applications include audio, intercom, control, energy management, and alarm circuits.
- In ducts, cable trays, or conduit
- In accordance with UL Subject 13 as Power-Limited Circuit Cable
- In class 3 circuits in accordance with NEC
- In accordance with UL Subject 2250 as Instrumentation Tray Cable (ITC)
- Permitted for use in Class 1 Division 2 industrial hazardous locations per NEC Article 501-4(b) for UL Type PLTC/ITC cables
- Per NEC Article 727 for Type PLTC/ITC