22 items
-
$0.00 /
- Approx LBS/MFT: 616
- AWG Size: 16
- Cond. Material: Bare Copper
-
$0.00 /
- Approx LBS/MFT: 734
- AWG Size: 16
- Cond. Material: Bare Copper
-
$0.00 /
- Approx LBS/MFT: 894
- AWG Size: 16
- Cond. Material: Bare Copper
-
$0.00 /
- Approx LBS/MFT: 1254
- AWG Size: 16
- Cond. Material: Bare Copper
-
$0.00 /
- Approx LBS/MFT: 1800
- AWG Size: 16
- Cond. Material: Bare Copper
-
$0.00 /
- Approx LBS/MFT: 186
- AWG Size: 16
- Cond. Material: Bare Copper
XLPE/PVC Instrumentation Cable with Overall Shielded Pairs/Triads Specifications
XLPE/PVC Instrumentation Cable Construction:
- Conductor: 18 AWG through 16 AWG bare, annealed copper per ASTM B3 Class B; stranding per ASTM B8
- Insulation: Flame Retardant Cross-linked Polyethylene (XLPE)
- Color-coded per ICEA Method 1: Pairs: Black and White Triads: Black, White, and Red
- Overall Shield: Aluminum/polyester in contact with stranded tinned copper drain wire
- Jacket: Flame Retardant and sunlight-resistant Polyvinylchloride (PVC) or Flame-Retardant, Arctic-Grade PVC
- Industrial Instrumentation Cable Options:
- Tinned copper conductor
- Class C Stranding
- Individual and overall shielded pairs/triads
- EVTC- Ethylene Propylene Rubber (EPR) insulation
- In accordance with UL subject 2250 as Instrumentation Tray Cable (ITC)
- Other constructions available upon request
XLPE/PVC Instrumentation Cable Ratings and Approvals:
- Voltage Rating: 300V or 600V
- Max. Temperature: 90°C wet or dry
- UL 1581
- UL 1581 VW-1
-
- IEEE 383
- 300V Cables:
- UL 13 Type PLTC
- 600V Cables:
- UL 1277 Type TC
- ICEA S-82-552
- ICEA S-73-532
- IEEE 1202
- CSA FT-4
- EPA 40 CFR, Part 261 for leachable lead content per TCLP
- OSHA acceptable
XLPE/PVC Instrumentation Cable Applications:
- Acceptable for use in free air or raceways in accordance with NEC
- Typical applications include audio, intercom, control, energy management, and alarm circuits
- In ducts, cable trays or conduit
- In accordance with UL Subject 13 as Power-Limited Circuit Cable
- In class 3 circuits in accordance with NEC
- Permitted for use in Class 1 Division 2 industrial hazardous locations per NEC
XLPE/PVC Instrumentation Cable Features:
- Ripcord applied to all cables with jacket thickness of 60 mils or less
- Arctic-Grade PVC Cables:
- Abrasion and chemical-resistant
- Sunlight and weather resistant
- Excellent electrical properties
- Meets cold bend test at -25°C