32 items
-
$0.00 /
- Approx LBS/MFT: 264
- AWG Size: 12
- Cond. Material: Tinned Copper
-
$0.00 /
- Approx LBS/MFT: 690
- AWG Size: 12
- Cond. Material: Tinned Copper
-
$0.00 /
- Approx LBS/MFT: 435
- AWG Size: 12
- Cond. Material: Tinned Copper
-
$0.00 /
- Approx LBS/MFT: 858
- AWG Size: 12
- Cond. Material: Tinned Copper
-
$0.00 /
- Approx LBS/MFT: 997
- AWG Size: 12
- Cond. Material: Tinned Copper
-
$0.00 /
- Approx LBS/MFT: 1393
- AWG Size: 12
- Cond. Material: Tinned Copper
XLPE/XL-CPE Unshielded Multi-Conductor Control Cable (Type TC) Specifications
XLPE/XL-CPE Unshielded Cable (Type TC) Construction:
- Conductor: 14 AWG thru 10 AWG fully annealed stranded tinned copper per ASTM B33
- Class B stranding per ASTM B8
- Insulation: Flame Retardant Cross-Linked Polyethylene (XLPE)
- Color-coded per ICEA Method 1; Table E-1
- Jacket: Cross-Linked Chlorinated Polyethylene (XL-CPE)
- Unshielded Control Cable (Type TC) Options:
- 2kV version
- Bare copper conductor
- Class C stranding
- E-2 Color Code
- Overall shielded multi-conductor
- Ethylene Propylene Rubber (EPR) insulation
- Thermoplastic Low-Smoke, Zero-Halogen (LSZH) jacket
- Flame Retardant, Polyvinylchloride (PVC) jacket
- Other constructions available upon request
XLPE/XL-CPE Unshielded Cable (Type TC) Ratings and Approvals:
- Voltage Rating: 600V
- Max. Temperature: 90°C, wet or dry
- Industry Approvals
- UL 44 Type XHHW-2
- UL 1277 Type TC
- UL 1581
- ICEA S-73-532
- ICEA S-95-658/NEMA WC74
- Flame Tests Compliances:
- UL 1581 VW-1
- UL 1277 Flame Test
- IEEE 383
- IEEE 1202
- CSA FT4
- ICEA T-29-520
- Other Compliances:
- Meets EPA 40 CFR, Part 261 for leachable lead content per TCLP method
- OSHA acceptable
XLPE/XL-CPE Unshielded Cable (Type TC) Features:
- Ripcord applied to all cables with jacket thickness of 60 mils or less
- Excellent physical, thermal and electrical properties
- Excellent moisture resistance
- Outstanding resistance to crush, compression cuts, and heat deformation
- Excellent flame resistance
- Oil resistant jacket
- "Heavy Duty" rating per ICEA standards
- Sunlight and weather resistant
- Excellent low-temperature cold bend characteristics
- Meets cold bend test at -35°C
XLPE/XL-CPE Unshielded Cable (Type TC) Applications:
- In free air, raceways, or direct burial
- In wet or dry locations
- Permitted for use in Class I, Div 2 industrial hazardous locations per NEC Article 501 and Class 1 circuits per NEC