The Lapp TC 600 S Tray Cable is suitable for use in plant expansion, contractor markets, A&E firm plant designs, tray wiring, and anywhere VNTC® cables are used. This shielded cable is easier to pull than a standard tray cable and features black numbered conductors with printed color code for easy identification. It is also UV-resistant, may be used in direct burial applications, and TC-ER approved so no conduit is needed.
42 items
-
$0.00 / 1000 FT
- Approx LBS/MFT: 68
- AWG Size: 16
- Cond. Material: Bare Copper
-
$0.00 / 1000 FT
- Approx LBS/MFT: 84
- AWG Size: 16
- Cond. Material: Bare Copper
-
$0.00 / 1000 FT
- Approx LBS/MFT: 97
- AWG Size: 16
- Cond. Material: Bare Copper
-
$0.00 / 1000 FT
- Approx LBS/MFT: 126
- AWG Size: 16
- Cond. Material: Bare Copper
-
$0.00 / 1000 FT
- Approx LBS/MFT: 170
- AWG Size: 16
- Cond. Material: Bare Copper
-
$0.00 / 1000 FT
- Approx LBS/MFT: 220
- AWG Size: 16
- Cond. Material: Bare Copper
Lapp TC 600 Shielded Tray Cable Specifications
TC 600 S Cable Construction:
- Conductors: Finely stranded bare copper
- Insulation: Specially blended PVC/Nylon
- Shielding: Foil tape (100% coverage); drain wire
- Jacket: Specially formulated black PVC
TC 600 S Cable Ratings and Approvals:
- Temperature Range:
- UL/CSA TC: -40°C to 90°C
- For flexible use: -5°C to 90°C
- For stationary use: -40°C to 105°C
- Nominal Voltage:
- UL/CSA TC: 600V
- UL WTTC: 1000V
- Minimum Bend Radius for Installation: 4 x cable diameter
- UL Approval:
- TC-ER per UL 1277
- MTW per UL 1063 (14 AWG and larger)
- WTTC per UL 2277
- Bus Drop Cable (14 AWG and larger, 3c & 4c)
-
AWM 20886
- Attributes:
- UL Oil Res I
- 75°C Wet; 90°C Dry
- Sunlight Resistant
- Direct Burial
- NFPA 79 2012
- CSA Approval:
- c(UL) CIC/TC FT4
- CSA AWM I/II A/B FT4
- NEC Approval
- Class 1 Division 2 per NEC Article 501
- CE Approved
- RoHS Compliant