The Lapp Tray II CY Cable is suitable for use in industrial plant expansions, automotive plants, tray wiring, and anywhere VNTC® cables are used. This shielded cable features an oil-resistant, pressure-extruded PVC jacket for improved flexibility and black numbered conductors for easy identification. It also features a double-laminated foil tape and tinned copper braid shield that provides 70 percent coverage. It is easier to pull than a standard tray cable and is TC-ER approved so no conduit is needed.
31 items
-
$0.00 / 1000 FT
- Approx LBS/MFT: 181
- AWG Size: 14
- Cond. Material: Bare Copper
-
$0.00 / 1000 FT
- Approx LBS/MFT: 220
- AWG Size: 14
- Cond. Material: Bare Copper
-
$0.00 / 1000 FT
- Approx LBS/MFT: 212
- AWG Size: 12
- Cond. Material: Bare Copper
-
$0.00 / 1000 FT
- Approx LBS/MFT: 335
- AWG Size: 12
- Cond. Material: Bare Copper
Lapp Tray II CY Cable Specifications
Tray II CY Cable Construction:
- Conductors: Finely stranded bare copper
- Insulation: Specially blended PVC/Nylon
- Color Code: Black with white numbers, plus green/yellow ground
- Jacket: Specially formulated oil-resistant black PVC
- Shielding: Double laminated foil tape; tinned copper braid (70% coverage)
Tray II CY Cable Ratings and Approvals:
- Temperature Range:
- UL/CSA TC: -25°C to 90°C
- For stationary use: -40°C to 90°C
- For flexible use: -5°C to 105°C
- Nominal Voltage:
- UL/CSA TC: 600V
- UL WTTC/CSA AWM: 1000V
- Minimum Bend Radius for Installation:
- < 1 AWG: 4 x cable diameter
- ≥ 1 AWG: 6 x cable diameter
- UL Approval:
- TC-ER per UL 1277
- MTW per UL 1063
- WTTC per UL 2277
- PLTC-ER per UL 13 (18-12 AWG)
- ITC-ER per UL 2250 (18-12 AWG)
- DP-1 per UL 1690
- AWM 20886
- Attributes:
- UL Oil Res I/II
- 70°C Wet; 90°C Dry
- Sunlight Resistant
- Direct Burial
- NFPA 79 2012
- NEC Approval: Class 1 Division 2 per NEC Article 501
- CSA Approval:
- CSA AWM I/II A/B FT 4
- c(UL) CIC/TC FT4
- Torsion Rated for Wind Market (± 90°/m) and (±150°/m)
- CE Approved
- RoHS Compliant
- MSHA-P07-KA050016-MSHA