The Lapp Control TM Cable is suitable for use in machine tools, food and beverage equipment, and processing equipment. This cable features flexible copper stranding, a pressure-extruded jacket, and number-coded conductors for easy connection. It is also TC-ER approved, meaning it may be installed off the machine and into an overhead tray without conduit.
36 items
Lapp Control TM Cable Specifications
Control TM Cable Construction:
- Conductors: Finely stranded bare copper (Class 5 fine wire)
- Insulation: Specially blended PVC/Nylon
- Color Code: Black with white numbers, plus green/yellow ground
- Jacket: Specially formulated gray PVC
Control TM Cable Ratings and Approvals:
- Temperature Range:
- UL/CSA TC: -25°C to +90°C
- For stationary use: -40 to +105°C
- For flexible use: -25°C to +90°C
- Nominal Voltage:
- UL/CSA TC: 600V
- UL WTTC: 1000V
- Test Voltage: 2000V
- Minimum Bend Radius for Installation: 4 x cable diameter
- UL:
- TC-ER per UL 1277
- MTW per UL 1063
- WTTC per UL 2277
- Bus Drop Cable (14 AWG & larger; 3c & 4c only)
- AWM 2587 & 21098 (Oil)
- Attributes:
- UL Oil Res I/II
- 75°C Wet; 90°C Dry
- Sunlight resistant
- Direct burial
- NFPA 79 2012
- NEC: Class 1, Division 2 per NEC Article 501
- Canada:
- c(UL) CIC/TC FT4
- CSA AWM I/II A/B FT4
- CE and RoHS Compliant
- Additional:
- Torsion rated for wind market (± 90°/m) & (± 150°/m)
- Passes impact and crush test per UL 1277 (except 20 AWG)
- Meets NFPA 79 2012 standards for wiring machinery (UL MTW)
- UL TC-ER approved